Difference between revisions of "Electrical Infrastructure"

From Asmbly Wiki
m
m
Line 2: Line 2:
  
 
* The 301 service feeds an outside service panel with two 100 A breakers. One of these feeds subpanel L8 and the other subpanel L9, both in the new metal shop.
 
* The 301 service feeds an outside service panel with two 100 A breakers. One of these feeds subpanel L8 and the other subpanel L9, both in the new metal shop.
* The 302 service has a 200A fused disconnect which feeds panel L10 in Ceramics.  L10 feeds L11 via a ??? A branch circuit breaker.
+
* The 302 service has a 200A fused disconnect which feeds panel L10 in Ceramics.  L10 feeds subpanel L11 via a 100 A branch circuit breaker.
 
* The 303 service feeds an outside service panel with one 200A breaker. This feeds subpanel L4.  L4 feeds subpanel L3 via a 100A branch circuit breaker.
 
* The 303 service feeds an outside service panel with one 200A breaker. This feeds subpanel L4.  L4 feeds subpanel L3 via a 100A branch circuit breaker.
* The 304 service has a 200A fused disconnect which feeds an outside service panel with two 100 A breakerss. One of these feeds subpanel L2 (via a switch disconnect SW, located on the south wall of the woodshop, east of the centerline1) and the other feeds subpanel L5. L5 feeds L6 via a 60 A branch circuit breaker.
+
* The 304 service has a 200A fused disconnect which feeds an outside service panel with two 100 A breakerss. One of these feeds subpanel L2 (via a switch disconnect SW, located on the south wall of the woodshop, east of the centerline1) and the other feeds subpanel L5. L5 feeds subpanel L6 via a 60 A branch circuit breaker.
 
* The 306 service has a 200A fused disconnect which feeds panel L7 in the multipurpose room. L7 feeds subpanel L8 via a 100A branch circuit breaker.
 
* The 306 service has a 200A fused disconnect which feeds panel L7 in the multipurpose room. L7 feeds subpanel L8 via a 100A branch circuit breaker.
  

Revision as of 17:41, 18 January 2025

Asmbly's facility is composed of five (out of six) units of 9701 Dessau Road building 3, each of which is equipped with its own "light commercial" 200A 3-phase 120/208V service. Our meters and outdoor disconnects are on the south side of the building.

  • The 301 service feeds an outside service panel with two 100 A breakers. One of these feeds subpanel L8 and the other subpanel L9, both in the new metal shop.
  • The 302 service has a 200A fused disconnect which feeds panel L10 in Ceramics. L10 feeds subpanel L11 via a 100 A branch circuit breaker.
  • The 303 service feeds an outside service panel with one 200A breaker. This feeds subpanel L4. L4 feeds subpanel L3 via a 100A branch circuit breaker.
  • The 304 service has a 200A fused disconnect which feeds an outside service panel with two 100 A breakerss. One of these feeds subpanel L2 (via a switch disconnect SW, located on the south wall of the woodshop, east of the centerline1) and the other feeds subpanel L5. L5 feeds subpanel L6 via a 60 A branch circuit breaker.
  • The 306 service has a 200A fused disconnect which feeds panel L7 in the multipurpose room. L7 feeds subpanel L8 via a 100A branch circuit breaker.

Restated in terms of panels:

Panel Location Capacity Supply Areas & Machines Directly Powered
L1 Wood shop, West wall 100 A L7 branch circuit Large CNC, Part of Fiber Laser (2 x 20 A)
L2 Wood shop, North wall 100 A 304 Service Panel (via SW1) Metal Shop, Air Compressor
L3 Wood shop, South wall, east side 100 A L4 100A branch circuit Wood Shop, incl. Planer, Jointer, Drill Press, Router, Sander,

Bandsaws, Chop/Miter Saw, Wood Lathes; Electronics Room

L4 Wood shop, South wall, east side 200 A * 303 Service Panel AC/Heating Units, Additional Wood Shop Tools
L5 Wood shop, South wall, west side 100 A * 304 Service Panel AC/Heating Units, Wood Shop Main Dust Collector
L6 Wood shop, South wall, west side 60 A L5 branch circuit Wood Shop, incl. Saw Stop Table Saw, Small CNC, Small Sanders
L7 Multipurpose Room 200 A * 306 Fused Disconnect Laser Room, 3D Printing Room, Textiles, Multipurpose Room, Lobby
L8 New Metal Shop (Northwest wall) 100 A 301 Service Panel Metal Shop
L9 New Metal Shop (Northwest wall) 100 A 301 Service Panel NW Lobby, Studios, Lights, Hallways
L10 Ceramics Shop (South wall) 200 A * 302 Fused Disconnect Ceramics
L11 Ceramics Shop (South wall) 100 A L10 branch circuit Ceramics

* Feeds another panel, limiting practical capacity.