− | Asmbly's facility is composed of | + | Asmbly's facility is composed of five (out of six) units of 9701 Dessau Road building 3, each of which is equipped with its own "light commercial" 200A 3-phase 120/208V service. Our meters and outdoor disconnects are on the south side of the building. |
− | * The 303 service feeds 200A | + | * The 301 service has a 200A fused disconnect which feeds an outside service panel with two 100 A breakers. One of these feeds subpanel L8 and the other subpanel L9, both located in the new metal shop. |
− | * The 304 service has a 200A fused disconnect | + | * The 302 service has a 200A fused disconnect which directly feeds panel L10 in Ceramics. |
− | * The 306 service has a 200A fused disconnect | + | * The 303 service feeds an outside service panel with one 200A breaker which feeds subpanel L4. L4 feeds subpanel L3 via a 100A branch circuit breaker. |
+ | * The 304 service has a 200A fused disconnect which feeds an outside service panel with two 100 A breakers. One of these feeds subpanel L2 (via a switch disconnect SW1, located on the south wall of the woodshop, east of the centerline) and the other feeds subpanel L5. L5 feeds subpanel L6 via a 60 A branch circuit breaker. | ||
+ | * The 306 service has a 200A fused disconnect which directly feeds panel L7 in the multipurpose room. L7 feeds subpanel L8 via a 100A branch circuit breaker. | ||
Restated in terms of panels: | Restated in terms of panels: | ||
Line 9: | Line 11: | ||
!Panel | !Panel | ||
!Location | !Location | ||
+ | !Capacity | ||
!Supply | !Supply | ||
!Areas & Machines Directly Powered | !Areas & Machines Directly Powered | ||
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
|L1 | |L1 | ||
− | | | + | |Wood shop, West wall |
− | + | |100 A | |
− | + | |L7 branch circuit | |
− | + | |Large CNC | |
− | |||
− | |||
− | | | ||
− | | | ||
|- | |- | ||
|L2 | |L2 | ||
− | | | + | |Wood shop, North wall |
− | |SW1 | + | |100 A |
− | |Metal Shop, | + | |304 Service Panel (via SW1) |
+ | |Old Metal Shop, Air Compressor | ||
|- | |- | ||
|L3 | |L3 | ||
− | | | + | |Wood shop, South wall, east side |
− | |L4 | + | |100 A |
+ | |L4 branch circuit | ||
|Wood Shop, incl. Planer, Jointer, Drill Press, Router, Sander, | |Wood Shop, incl. Planer, Jointer, Drill Press, Router, Sander, | ||
Bandsaws, Chop/Miter Saw, Wood Lathes; Electronics Room | Bandsaws, Chop/Miter Saw, Wood Lathes; Electronics Room | ||
|- | |- | ||
|L4 | |L4 | ||
− | | | + | |Wood shop, South wall, east side |
− | |303 | + | |200 A * |
− | |AC/Heating Units | + | |303 Service Panel |
+ | |AC/Heating Units, Additional Wood Shop Tools | ||
|- | |- | ||
|L5 | |L5 | ||
− | | | + | |Wood shop, South wall, west side |
− | | | + | |100 A * |
− | |AC/Heating Units | + | |304 Service Panel |
+ | |AC/Heating Units, Wood Shop Main Dust Collector | ||
|- | |- | ||
|L6 | |L6 | ||
− | | | + | |Wood shop, South wall, west side |
− | | | + | |60 A |
− | |Wood Shop, incl. Saw Stop Table Saw, Small CNC, | + | |L5 branch circuit |
+ | |Wood Shop, incl. Saw Stop Table Saw, Small CNC, Small Sanders | ||
|- | |- | ||
|L7 | |L7 | ||
|Multipurpose Room | |Multipurpose Room | ||
+ | |200 A * | ||
|306 Fused Disconnect | |306 Fused Disconnect | ||
|Laser Room, 3D Printing Room, Textiles, Multipurpose Room, Lobby | |Laser Room, 3D Printing Room, Textiles, Multipurpose Room, Lobby | ||
|- | |- | ||
|L8 | |L8 | ||
− | | | + | |New Metal Shop (Northwest wall) |
− | | | + | |100 A |
− | | | + | |301 Service Panel |
+ | |New Metal Shop | ||
+ | |- | ||
+ | |L9 | ||
+ | |New Metal Shop (Northwest wall) | ||
+ | |100 A | ||
+ | |301 Service Panel | ||
+ | |NW Lobby, Studios, Lights, Hallways | ||
+ | |- | ||
+ | |L10 | ||
+ | |Ceramics Shop (South wall) | ||
+ | |200 A | ||
+ | |302 Fused Disconnect | ||
+ | |Ceramics | ||
|} | |} | ||
+ | <nowiki>*</nowiki> Feeds another panel, limiting practical capacity. | ||
[[Category:Operations]] | [[Category:Operations]] | ||
[[Category:Infrastructure]] | [[Category:Infrastructure]] |
Latest revision as of 02:52, 20 January 2025
Asmbly's facility is composed of five (out of six) units of 9701 Dessau Road building 3, each of which is equipped with its own "light commercial" 200A 3-phase 120/208V service. Our meters and outdoor disconnects are on the south side of the building.
- The 301 service has a 200A fused disconnect which feeds an outside service panel with two 100 A breakers. One of these feeds subpanel L8 and the other subpanel L9, both located in the new metal shop.
- The 302 service has a 200A fused disconnect which directly feeds panel L10 in Ceramics.
- The 303 service feeds an outside service panel with one 200A breaker which feeds subpanel L4. L4 feeds subpanel L3 via a 100A branch circuit breaker.
- The 304 service has a 200A fused disconnect which feeds an outside service panel with two 100 A breakers. One of these feeds subpanel L2 (via a switch disconnect SW1, located on the south wall of the woodshop, east of the centerline) and the other feeds subpanel L5. L5 feeds subpanel L6 via a 60 A branch circuit breaker.
- The 306 service has a 200A fused disconnect which directly feeds panel L7 in the multipurpose room. L7 feeds subpanel L8 via a 100A branch circuit breaker.
Restated in terms of panels:
Panel | Location | Capacity | Supply | Areas & Machines Directly Powered |
---|---|---|---|---|
L1 | Wood shop, West wall | 100 A | L7 branch circuit | Large CNC |
L2 | Wood shop, North wall | 100 A | 304 Service Panel (via SW1) | Old Metal Shop, Air Compressor |
L3 | Wood shop, South wall, east side | 100 A | L4 branch circuit | Wood Shop, incl. Planer, Jointer, Drill Press, Router, Sander,
Bandsaws, Chop/Miter Saw, Wood Lathes; Electronics Room |
L4 | Wood shop, South wall, east side | 200 A * | 303 Service Panel | AC/Heating Units, Additional Wood Shop Tools |
L5 | Wood shop, South wall, west side | 100 A * | 304 Service Panel | AC/Heating Units, Wood Shop Main Dust Collector |
L6 | Wood shop, South wall, west side | 60 A | L5 branch circuit | Wood Shop, incl. Saw Stop Table Saw, Small CNC, Small Sanders |
L7 | Multipurpose Room | 200 A * | 306 Fused Disconnect | Laser Room, 3D Printing Room, Textiles, Multipurpose Room, Lobby |
L8 | New Metal Shop (Northwest wall) | 100 A | 301 Service Panel | New Metal Shop |
L9 | New Metal Shop (Northwest wall) | 100 A | 301 Service Panel | NW Lobby, Studios, Lights, Hallways |
L10 | Ceramics Shop (South wall) | 200 A | 302 Fused Disconnect | Ceramics |
* Feeds another panel, limiting practical capacity.