* The 303 service feeds 200A panel L4 via a main breaker outside.  L4 feeds subpanel L3 via a 100A branch circuit breaker.
 
* The 303 service feeds 200A panel L4 via a main breaker outside.  L4 feeds subpanel L3 via a 100A branch circuit breaker.
* The 304 service has a 200A fused disconnect feeding a 200A main panel outside (SP6), which feeds subpanels L2 (via a switch disconnect SW1) and L5 via 100A branch circuit breakers. L5 feeds L6 via a ??? A branch circuit breaker.
+
* The 304 service has a 200A fused disconnect feeding a 200A main panel outside (SP6), which feeds subpanels L2 (via a switch disconnect SW1) and L5 via 100A branch circuit breakers. L5 feeds L6 via a 60 A branch circuit breaker.
 
* The 306 service has a 200A fused disconnect feeding panel L7 (in the multipurpose room). L7 feeds subpanel L8 via a 100A branch circuit breaker.
 
* The 306 service has a 200A fused disconnect feeding panel L7 (in the multipurpose room). L7 feeds subpanel L8 via a 100A branch circuit breaker.
  
Line 30: Line 30:
 
|Main shop, North wall
 
|Main shop, North wall
 
|SW1
 
|SW1
|Metal Shop, Air Compressor (3ø supply)
+
|Metal Shop, Part of Fiber Laser (30 A) Air Compressor
 
|-
 
|-
 
|L3
 
|L3
 
|Main shop, South wall, east side
 
|Main shop, South wall, east side
 
|L4 100A branch circuit
 
|L4 100A branch circuit
|Wood Shop, incl. Planer, Jointer, Drill Press, Router, Sander, Band Saws;
+
|Wood Shop, incl. Planer, Jointer, Drill Press, Router, Sander, Band Saws,
Electronics Room
+
Chop/Miter Saw, Wood Lathes; Electronics Room
 
|-
 
|-
 
|L4
 
|L4
Line 46: Line 46:
 
|Main shop, South wall, west side
 
|Main shop, South wall, west side
 
|SP6 100A branch circuit
 
|SP6 100A branch circuit
|Wood Shop, incl. Saw Stop, Chop Saw
+
|AC/Heating Units; Wood Shop Main Dust Collector
 
|-
 
|-
 
|L6
 
|L6
 
|Main shop, South wall, west side
 
|Main shop, South wall, west side
|L5 ??? A branch circuit
+
|L5 60 A branch circuit
|Wood Shop, incl. Dust Collector (?), Small CNC, Sanding Table
+
|Wood Shop, incl. Saw Stop Table Saw, Small CNC, Sanding Table
 
|-
 
|-
 
|L7
 
|L7
Line 61: Line 61:
 
|Main shop, West wall
 
|Main shop, West wall
 
|L7 100A branch circuit
 
|L7 100A branch circuit
|Large CNC, Part of Fiber Laser
+
|Large CNC, Part of Fiber Laser (2 x 20 A)
 
|}
 
|}
 
[[Category:Operations]]
 
[[Category:Operations]]

Revision as of 02:15, 3 October 2022

Asmbly's facility is composed of three separate units of 9701 Dessau Road building 3, each of which is equipped with its own "light commercial" 200A 3-phase 120/208V service. Our meters and outdoor disconnects are on the south side of the building around the corner from the laser exhausts.

  • The 303 service feeds 200A panel L4 via a main breaker outside. L4 feeds subpanel L3 via a 100A branch circuit breaker.
  • The 304 service has a 200A fused disconnect feeding a 200A main panel outside (SP6), which feeds subpanels L2 (via a switch disconnect SW1) and L5 via 100A branch circuit breakers. L5 feeds L6 via a 60 A branch circuit breaker.
  • The 306 service has a 200A fused disconnect feeding panel L7 (in the multipurpose room). L7 feeds subpanel L8 via a 100A branch circuit breaker.

Restated in terms of panels:

Panel Location Supply Areas & Machines Directly Powered
SP6 Outside 304 Fused Disconnect
L1 Unused (Stored in NE closet) N/A
SW1 Main shop, South wall, east side SP6 100 A branch circuit
L2 Main shop, North wall SW1 Metal Shop, Part of Fiber Laser (30 A) Air Compressor
L3 Main shop, South wall, east side L4 100A branch circuit Wood Shop, incl. Planer, Jointer, Drill Press, Router, Sander, Band Saws,

Chop/Miter Saw, Wood Lathes; Electronics Room

L4 Main shop, South wall, east side 303 Main Breaker AC/Heating Units
L5 Main shop, South wall, west side SP6 100A branch circuit AC/Heating Units; Wood Shop Main Dust Collector
L6 Main shop, South wall, west side L5 60 A branch circuit Wood Shop, incl. Saw Stop Table Saw, Small CNC, Sanding Table
L7 Multipurpose Room 306 Fused Disconnect Laser Room, 3D Printing Room, Textiles, Multipurpose Room, Lobby
L8 Main shop, West wall L7 100A branch circuit Large CNC, Part of Fiber Laser (2 x 20 A)