Asmbly's facility is composed of three separate units of 9701 Dessau Road building 3, each of which is equipped with its own "light commercial" 200A 3-phase 120/208V service.  Our meters and outdoor disconnects are on the south side of the building around the corner from the laser exhausts.
 
Asmbly's facility is composed of three separate units of 9701 Dessau Road building 3, each of which is equipped with its own "light commercial" 200A 3-phase 120/208V service.  Our meters and outdoor disconnects are on the south side of the building around the corner from the laser exhausts.
  
* The 303 service feeds 200A panel L4 via a main breaker outside.  L4 feeds subpanel L3 via a 100A branch circuit breaker.
+
* The 301 service feeds an outside service panel with two 100 A breakers. One of these feeds subpanel L8 and the other subpanel L9, both in the new metal shop.
* The 304 service has a 200A fused disconnect feeding a 200A main panel outside (SP6), which feeds subpanels L2 (via a switch disconnect SW1) and L5 via 100A branch circuit breakers. L5 feeds L6 via a 60 A branch circuit breaker.
+
* The 302 service has a 200A fused disconnect which feeds panel L10 in Ceramics.  L10 feeds L11 via a ??? A branch circuit breaker.
* The 306 service has a 200A fused disconnect feeding panel L7 (in the multipurpose room). L7 feeds subpanel L8 via a 100A branch circuit breaker.
+
* The 303 service feeds an outside service panel with one 200A breaker. This feeds subpanel L4.  L4 feeds subpanel L3 via a 100A branch circuit breaker.
 +
* The 304 service has a 200A fused disconnect which feeds an outside service panel with two 100 A breakerss. One of these feeds subpanel L2 (via a switch disconnect SW, located on the south wall of the woodshop, east of the centerline1) and the other feeds subpanel L5. L5 feeds L6 via a 60 A branch circuit breaker.
 +
* The 306 service has a 200A fused disconnect which feeds panel L7 in the multipurpose room. L7 feeds subpanel L8 via a 100A branch circuit breaker.
  
 
Restated in terms of panels:
 
Restated in terms of panels:
Line 9: Line 11:
 
!Panel
 
!Panel
 
!Location
 
!Location
 +
!Capacity
 
!Supply
 
!Supply
 
!Areas & Machines Directly Powered
 
!Areas & Machines Directly Powered
|-
 
|SP6
 
|Outside
 
|304 Fused Disconnect
 
|
 
 
|-
 
|-
 
|L1
 
|L1
|Unused (Stored in NE closet)
+
|Wood shop, West wall
|N/A
+
|100 A
|
+
|L7 100A branch circuit
|-
+
|Large CNC, Part of Fiber Laser (2 x 20 A)
|SW1
 
|Main shop, South wall, east side
 
|SP6 100 A branch circuit
 
|
 
 
|-
 
|-
 
|L2
 
|L2
|Main shop, North wall
+
|Wood shop, North wall
|SW1
+
|100 A
|Metal Shop, Part of Fiber Laser (30 A) Air Compressor
+
|304 Service Panel (via SW1)
 +
|Metal Shop, Air Compressor
 
|-
 
|-
 
|L3
 
|L3
|Main shop, South wall, east side
+
|Wood shop, South wall, east side
 +
|100 A
 
|L4 100A branch circuit
 
|L4 100A branch circuit
 
|Wood Shop, incl. Planer, Jointer, Drill Press, Router, Sander,
 
|Wood Shop, incl. Planer, Jointer, Drill Press, Router, Sander,
Line 39: Line 35:
 
|-
 
|-
 
|L4
 
|L4
|Main shop, South wall, east side
+
|Wood shop, South wall, east side
|303 Main Breaker
+
|200 A *
|AC/Heating Units
+
|303 Service Panel
 +
|AC/Heating Units, Additional Wood Shop Tools
 
|-
 
|-
 
|L5
 
|L5
|Main shop, South wall, west side
+
|Wood shop, South wall, west side
|SP6 100A branch circuit
+
|100 A *
|AC/Heating Units; Wood Shop Main Dust Collector
+
|304 Service Panel
 +
|AC/Heating Units, Wood Shop Main Dust Collector
 
|-
 
|-
 
|L6
 
|L6
|Main shop, South wall, west side
+
|Wood shop, South wall, west side
 +
|60 A
 
|L5 60 A branch circuit
 
|L5 60 A branch circuit
|Wood Shop, incl. Saw Stop Table Saw, Small CNC, Sanding Table
+
|Wood Shop, incl. Saw Stop Table Saw, Small CNC, Small Sanders
 
|-
 
|-
 
|L7
 
|L7
 
|Multipurpose Room
 
|Multipurpose Room
 +
|200 A *
 
|306 Fused Disconnect
 
|306 Fused Disconnect
 
|Laser Room, 3D Printing Room, Textiles, Multipurpose Room, Lobby
 
|Laser Room, 3D Printing Room, Textiles, Multipurpose Room, Lobby
 
|-
 
|-
 
|L8
 
|L8
|Main shop, West wall
+
|New Metal Shop (Northwest wall)
|L7 100A branch circuit
+
|100 A
|Large CNC, Part of Fiber Laser (2 x 20 A)
+
|301 Service Panel
 +
|Metal Shop
 +
|-
 +
|L9
 +
|New Metal Shop (Northwest wall)
 +
|100 A
 +
|301 Service Panel
 +
|NW Lobby, Studios, Lights, Hallways
 +
|-
 +
|L10
 +
|Ceramics Shop (South wall)
 +
|200 A *
 +
|302 Fused Disconnect
 +
|Ceramics
 +
|-
 +
|L11
 +
|Ceramics Shop (South wall)
 +
|
 +
|L10 ?? A branch circuit
 +
|Ceramics
 
|}
 
|}
 +
<nowiki>*</nowiki> Feeds another panel, limiting practical capacity.
 
[[Category:Operations]]
 
[[Category:Operations]]
 
[[Category:Infrastructure]]
 
[[Category:Infrastructure]]

Revision as of 17:27, 18 January 2025

Asmbly's facility is composed of three separate units of 9701 Dessau Road building 3, each of which is equipped with its own "light commercial" 200A 3-phase 120/208V service. Our meters and outdoor disconnects are on the south side of the building around the corner from the laser exhausts.

  • The 301 service feeds an outside service panel with two 100 A breakers. One of these feeds subpanel L8 and the other subpanel L9, both in the new metal shop.
  • The 302 service has a 200A fused disconnect which feeds panel L10 in Ceramics. L10 feeds L11 via a ??? A branch circuit breaker.
  • The 303 service feeds an outside service panel with one 200A breaker. This feeds subpanel L4. L4 feeds subpanel L3 via a 100A branch circuit breaker.
  • The 304 service has a 200A fused disconnect which feeds an outside service panel with two 100 A breakerss. One of these feeds subpanel L2 (via a switch disconnect SW, located on the south wall of the woodshop, east of the centerline1) and the other feeds subpanel L5. L5 feeds L6 via a 60 A branch circuit breaker.
  • The 306 service has a 200A fused disconnect which feeds panel L7 in the multipurpose room. L7 feeds subpanel L8 via a 100A branch circuit breaker.

Restated in terms of panels:

Panel Location Capacity Supply Areas & Machines Directly Powered
L1 Wood shop, West wall 100 A L7 100A branch circuit Large CNC, Part of Fiber Laser (2 x 20 A)
L2 Wood shop, North wall 100 A 304 Service Panel (via SW1) Metal Shop, Air Compressor
L3 Wood shop, South wall, east side 100 A L4 100A branch circuit Wood Shop, incl. Planer, Jointer, Drill Press, Router, Sander,

Bandsaws, Chop/Miter Saw, Wood Lathes; Electronics Room

L4 Wood shop, South wall, east side 200 A * 303 Service Panel AC/Heating Units, Additional Wood Shop Tools
L5 Wood shop, South wall, west side 100 A * 304 Service Panel AC/Heating Units, Wood Shop Main Dust Collector
L6 Wood shop, South wall, west side 60 A L5 60 A branch circuit Wood Shop, incl. Saw Stop Table Saw, Small CNC, Small Sanders
L7 Multipurpose Room 200 A * 306 Fused Disconnect Laser Room, 3D Printing Room, Textiles, Multipurpose Room, Lobby
L8 New Metal Shop (Northwest wall) 100 A 301 Service Panel Metal Shop
L9 New Metal Shop (Northwest wall) 100 A 301 Service Panel NW Lobby, Studios, Lights, Hallways
L10 Ceramics Shop (South wall) 200 A * 302 Fused Disconnect Ceramics
L11 Ceramics Shop (South wall) L10 ?? A branch circuit Ceramics

* Feeds another panel, limiting practical capacity.