Difference between revisions of "Electrical Infrastructure"
From Asmbly Wiki
m (Inserted L6 capacity, fixed equipment lists) |
m (Formatting) |
||
Line 35: | Line 35: | ||
|Main shop, South wall, east side | |Main shop, South wall, east side | ||
|L4 100A branch circuit | |L4 100A branch circuit | ||
− | |Wood Shop, incl. Planer, Jointer, Drill Press, Router, Sander, Band Saws, | + | |Wood Shop, incl. Planer, Jointer, Drill Press, Router, Sander, |
− | Chop/Miter Saw, Wood Lathes; Electronics Room | + | Band Saws, Chop/Miter Saw, Wood Lathes; Electronics Room |
|- | |- | ||
|L4 | |L4 |
Revision as of 02:28, 3 October 2022
Asmbly's facility is composed of three separate units of 9701 Dessau Road building 3, each of which is equipped with its own "light commercial" 200A 3-phase 120/208V service. Our meters and outdoor disconnects are on the south side of the building around the corner from the laser exhausts.
- The 303 service feeds 200A panel L4 via a main breaker outside. L4 feeds subpanel L3 via a 100A branch circuit breaker.
- The 304 service has a 200A fused disconnect feeding a 200A main panel outside (SP6), which feeds subpanels L2 (via a switch disconnect SW1) and L5 via 100A branch circuit breakers. L5 feeds L6 via a 60 A branch circuit breaker.
- The 306 service has a 200A fused disconnect feeding panel L7 (in the multipurpose room). L7 feeds subpanel L8 via a 100A branch circuit breaker.
Restated in terms of panels:
Panel | Location | Supply | Areas & Machines Directly Powered |
---|---|---|---|
SP6 | Outside | 304 Fused Disconnect | |
L1 | Unused (Stored in NE closet) | N/A | |
SW1 | Main shop, South wall, east side | SP6 100 A branch circuit | |
L2 | Main shop, North wall | SW1 | Metal Shop, Part of Fiber Laser (30 A) Air Compressor |
L3 | Main shop, South wall, east side | L4 100A branch circuit | Wood Shop, incl. Planer, Jointer, Drill Press, Router, Sander,
Band Saws, Chop/Miter Saw, Wood Lathes; Electronics Room |
L4 | Main shop, South wall, east side | 303 Main Breaker | AC/Heating Units |
L5 | Main shop, South wall, west side | SP6 100A branch circuit | AC/Heating Units; Wood Shop Main Dust Collector |
L6 | Main shop, South wall, west side | L5 60 A branch circuit | Wood Shop, incl. Saw Stop Table Saw, Small CNC, Sanding Table |
L7 | Multipurpose Room | 306 Fused Disconnect | Laser Room, 3D Printing Room, Textiles, Multipurpose Room, Lobby |
L8 | Main shop, West wall | L7 100A branch circuit | Large CNC, Part of Fiber Laser (2 x 20 A) |